ID 110454
| Value for quantization of measurement system increments is zero. | ||||
| Description | The value for the quantization of measurement system increments is zero. It must be greater zero. The default setting consists of one increment. For spindle revolution monitoring (see FCT-S1// Section: Spindle monitoring and during the check of the exact stop of axes (see P-AXIS-00236), a check is made whether the current values are within a specified tolerance. Parameter P-AXIS-00323 is the minimum size of the tolerance window after conversion of the tolerance limits into the resolution of the measurement system (default setting: 1 increment). | |||
| Response | Class | 1 | Correct parameter P-AXIS-00323 to default value 1 | |
| Solution | Class | 1 | Correct parameter P-AXIS-00323 | |
| Parameter | %1: | Logical axis number [-] | ||
| Logical axis number of affected axis, see P-AXIS-00016 | ||||
| %2: | Incorrect value [-] | |||
| Specified value, see P-AXIS-00323 | ||||
| %3: | Corrected value [-] | |||
| Corrected value see P-AXIS-00323 | ||||
| Error type | - | |||
| 
 | ||||